No.
Name
Setting Range
Default
E5-03
Pulse Train Input Voltage Bias
-100.0 to 100.0%
0.0%
E5-04 Pulse Train Input Filter Time
Sets the pulse train input primary filter time in seconds.
No.
Name
Setting Range
Default
E5-04
Pulse Train Input Filter Time
0.00 to 2.00 s
0.10 s
E5- 05 Pulse Train Input Minimum Frequency
Sets the minimum frequency detected by the pulse train input in units of 0.1 Hz.
· When the pulse input frequency drops below this level, the pulse input value becomes
0.0Hz.
· Enabled when E5-00 = 0, 1 or 2.
· When E5-00 = 3 (Simple Closed-Loop V/F Control), the minimum frequency becomes the
settitng for F1-04.
No.
Name
Setting Range
Default
E5-05
Pulse Train Input Minimum
Frequency
0.1 to 1000.0 Hz
0.5 Hz
E5-06 Pulse Train Monitor Selection
Selects the pulse train monitor.
No.
Name
Setting Range
Default
E5-06
Pulse Train Monitor Selection
0 to 4
0
Sets the function of pulse train output terminal MP.
Setting
Function
0
Frequency Command
1
Output Frequency
2
Soft Starter Output Frequency
3
PID Feedback Value
4
PID Target Value
Notice: When using pulse train monitor, set the peripheral devices according to the load
conditions below. Failure to comply could cause low per formance or machinery damage.
When used as a common collector output
Output voltage (insulation type) VRL ( V)
Load resistance ( kΩ)
5 V or above
1.5 kΩ or above
8 V or above
4.0 kΩ or above