205
Monitors the drive cumulative output power usage. The value
is shown as a 9-digit number displayed across two monitors
U3-08 and U3-09.
Example: 12345678.9 kWh is displayed as:
U3-08: 678.9 kWh
U9-09: 12345 MWh
Displays the peak current value during operation
Peak Hold Output
Frequency
Displays the output frequency when the peak current
displayed in U3-10 occurred.
Motor Overload
Estimate (oL1)
Displays the value of the motor overload detection
accumulator. An oL1 will be triggered when reaching 100%.
Frequency
Command Source
Selection
Displays the source for the frequency command as XY-nn.
X: Command Used
1: Command 1
2: Command 2
Y-nn: Frequency Command Source
0-01: Keypad
1-01: Analog input (Terminal AI 1)
1-02: Analog input (Terminal AI 2)
2-02 to 2-16: Multi-step speed command
2-17: Jog frequency command
3-01: PID frequency command
4-01: Terminal UP/ DOWN
5-01: Modbus communication
6-01: Pulse train command
Run Command
Source Selection
Displays the source for the frequency command as XY-nn.
XY-nn=00-00: Local
X: Command Used
1: Command 1
2: Command 2
Y-nn: Command Source
0-00: Keypad
0-01: Control Circuit Terminal (Sequence Control Input)
0-02: Modbus communication
Drive Overload
Estimate (oL2)
Displays the value of the drive overload detection
accumulator. An oL2 will be triggered when reaching 100%.