47
High voltage: 10 ~ 24V
Low voltage: 0 ~ 0.5V
For digital inputs, switch Sink /
Source mode must be external
connection
High-speed pulse signal common terminal
Digital control signal common terminal
Multi-Function
Analog Inputs
Auxiliary power terminal +10V
Analog input terminal 1
(main frequency command)
Voltage input
0 to 10V / -10V to +10V
Analog input terminal 2
(auxiliary frequency command)
Voltage or current input
(Selectable). 0 or 4 to
20mA, 0 to 10V, 0 to 5V
The ground terminal for
control signals to avoid
interference. Use
shielded cables only.
+24V auxiliary power terminal for analog input
Digital control signal
power + 24V
(INT port selection by
short-circuiting)
INT: short circuit, internal
offer
+ 24V / 200mA: open,
externally supplied +
24V
Table 4.3.1.2 Control Circuit Output Terminals
Multi-Function
Photocoupler
Output
Photocoupler Output terminal 1 (zero speed)
Photocoupler Output
48 V, 2 to 50 mA
Photocoupler Output terminal 2 (speed agree)
RS485 communication terminal, standard RS485 interface, use twisted pair
or shielded wire
Multi-Function
Analog Output
Programmable analog output terminal (output
frequency)
Voltage Output
0 to 10V, -10 to +10V
Multi-function analog output terminal (output
current )
Voltage or current
output (Selectable) 0 or