0 : V/F Control   
This  method  is  recommended  for  those  applications  without  the  need  of  fast  response, 
accurate speed control. Select this method also when using a single  drive to run more than 
one  motors, the motor  parameters  are unknown  or  Auto-Tuning cannot  be  performed.  The 
speed control range is 1 : 40.   
1 : SVVC 
  A1-03  Reset 
Resets  parameter  settings  to  default  settings.  After  resetting  parameters,  the  value  will 
automatically set to 0. 
0: N/A 
2538: Resets 2-Wire Sequence/ 50Hz / 380V 
2541: Resets 2-Wire Sequence / 50Hz / 415V   
2544: Resets 2-Wire Sequence / 50Hz / 440V   
2546: Resets 2-Wire Sequence / 50Hz / 460V   
2638: Resets 2-Wire Sequence / 60Hz / 380V   
2641: Resets 2-Wire Sequence / 60Hz / 415V   
2644: Resets 2-Wire Sequence / 60Hz / 440V   
2646: Resets 2-Wire Sequence / 60Hz / 460V   
3538: Resets 3-Wire Sequence / 50Hz / 380V   
3541: Resets 3-Wire Sequence / 50Hz / 415V   
3544: Resets 3-Wire Sequence / 50Hz / 440V   
3546: Resets 3-Wire Sequence / 50Hz / 460V   
3646: Resets 3-Wire Sequence / 60Hz / 460V 
 
Note:   
  The parameter listed in Table 6.1 will not be reset when setting 2220 or 3330 to A1-03.