  Frequency command as a single source b1-00 (or b1-07) set of values 
1  :Enabled 
Frequency command as   
B1-00 and b1-07 frequency instruction set of the superposition of two sources of value, the 
frequency superimposed b1-00 and b1-07 can not set to the same source, otherwise it will 
be tripped OPE13 error, but not in this simulation input limit  (when superimposed b1-00 
and  b1-07  can  simultaneously  set to  1). Frequency superposition function is valid  only  in 
Remote mode, Local mode is invalid 
 
Note : b1-00 and b1-07 is set to analog input simultaneously superimposed use, it will be forced 
to specify as input source b1-00 of AI1, AI2 as the input source b1-07. If b1-00 and b1-07 are not 
all 1, setting b1-09 = 1, E3-01 = 0, E3-07 = 0, it will be tripped OPE07 error 
  b1- 10  Run Command at Power up     
Determines to accept or ignore an active Run command from Remote during power up. 
0 : Ignore 
Drive ignores an active run command during power up.   
Note: The LED indicator blinks when there is an active Run command from Remote during power up. The drive can 
start only when the Run command is removed and entered again.   
1 : Accept 
Drive  accepts an active Run command  from Remote  during  power  up  and starts  the  motor 
immediately   
WARNING! The drive will run the motor immediately at power up if there an active Run command from Remote. 
Ensure the protection measures are taken and clear all personnel from the electrical connections and the running 
machinery prior to switching command sources. Failure to comply could cause serious injury.     
  b1- 12     Allowing Local/Remote selection during run   
Allowing Local/Remote selection   
during run   
0  :Disable