5-9
1) TCP/IP setting
Classification
Description
High-speed
link station No.
Specify station No. for High-speed link communication between LSIS PLCs’ FEnet
I/F modules, which shall not be duplicated identically to the correspondent
communication module.
Media
Select media to use.
AUTO (electric) : automatically detects the module presently installed.
10M/HALF : 10MBps Half Duplex electric
10M/FULL : 10MBps Full Duplex electric
100M/HALF : 100MBps Half Duplex electric
100M/FULL : 10MBps Full Duplex electric
FX/100M/HALF : 100MBps Half Duplex optical
FX/100M/FULL : 100MBps Full Duplex optical
IP address
Specify the IP Address of the applicable FEnet I/F module.
Subnet mask
Value necessary to check if destination station
is on the same network of the
applicable station.
Gateway
IP address of Gateway or R
outer to transmit/receive data through the public
network or a network different from the network where the
applicable FEnet
module is included.
DNS server
Specify the IP address of domain name server.
DHCP
(note1)
Check DHCP option when not fixed but dynamic IP is to be used (ADSL).
Relay
Using when send frame received at one port to another port.
Reception
wating time
If there is no request during the specified time from the host PC or MMI connected
for dedicated communication, it will end the dedicate
d service connection
regardless of normal ending procedures supposing that the higher level
system is
with error. This time is used in dedicated service to reset the channel
when any
error occurs on the destination station or the cable is disconnected.
Number of
dedicated
connections
Max. number of TCP dedicated services accessible at a time. (1~16)
2) Driver (server) setting
Classification
Description
XGT server
Set when operated as dedicated communication server (slave)
Modbus TCP/IP server
Set when operated as Modbus server driver (slave)
3) Host table setting
Classification
Description
Enable host table
Access allowed to applicable module of IP address registered in host table
(unregistered client(IP address) is prohibited from connection when enabled)