Chapter 5 XG5000 Program
5-14
(2) Setting communication module
[fig.5.3.3] Setting of communication module and communication period
Classification
Description
Communication
module settings
Module type
Select FEnet.
Base No.
Select Base No. the module is installed on.
(Main Base : 00)
Slot No. Select Slot No. the module is installed on.
Communication
period settings
Period type
Set the data transmission period.
(available range is 20ms~10sec)
Output data setup
in case of
emergency
Latch
Maintain and send the latest data received from CPU.
It is seen that it is cleared if CPU sends data as 0
even though latch is set. Make sure to check the
emergency output data setting of CPU.
Clear
It sends by setting received High-speed Link data as 0
in ignoring data from CPU. If emergency data is set as
‘clear’ in emergency output data setting of XG5000
High-
speed Link module setting even though
emergency output data setting of device area of High-
speed Link sending part is set as latch in CPU, the
data set as 0 is sent. Make sure to set it after
checking desired operation.

Table of Contents