INSTALLATION & USER'S MANUAL SL2 Page 15
Ebox alarm relay
The searchlights electrical and mechanical condition are constantly monitored and if there is a
malfunction in the system this is indicated by icons in the panel display with clarifying warning
messages found in the panels status menu, see 16.7 Status.
The control box also has a relay output that can be connected to the alarm monitoring system;
see below and the wiring diagram for connection details
Errors that trigger the alarm output.
Transmission issues on the CAN bus
Check for loose CAN-wires in
the electrical box or junction
points (if any) and contact
Luminell.
Overcurrent protection triggered;
movement blocked
Check that the searchlight is
able to rotate freely.
In winter, heavy icing can be the
cause of this error.
Overvoltage protection triggered, voltage
to searchlight motordriver/s have
exceeded 40Vdc.
Reset the error, if error recurs
repeatedly, please contact
Luminell.
Undervoltage protection triggered, voltage
to searchlight motordriver/s has fallen
below 8,5Vdc
Reset the error, if error recurs
repeatedly, please contact
Luminell.
OPWDT
(message in
box only)
Ethernet communication broken to all
panels, see (4.1) OP WDT.
Fault auto-resets if contact is restored with
at least one panel.
Check Ethernet wires and
connections to panel(s) and
switch.