Page 66 INSTALLATION & USER'S MANUAL SL2
Category 2: Diagnostics (support tool)
In this chapter all of Category 2 menu items will be explained.
(2.1) Start
Press the OK button to run the on-board diagnostic test suite to sense the electrical and
mechanical condition of the searchlight. (contact Luminell for help with this feature).
T1. Measurement of voltage and current when the searchlight is in “non operating mode”
T2 (HCW). Measurement of current drawn by the horizontal motor; motor rotates clockwise for
30 seconds.
T3 (HCCW). Measurement of current drawn by the horizontal motor; motor rotates
counterclockwise for 30 seconds.
T4 (VCW). Measurement of current drawn by the vertical motor; motor rotates clockwise for 30
seconds.
T5 (VCCW). Measurement of current drawn by the vertical motor; motor rotates
counterclockwise for 30 seconds and the value is temporary stored.
T6 /T7 (not valid for this model).
T8 (H MAG). Test of horizontal magnetic sensor; the horizontal motor is running at full speed for
a predetermined time and number of triggers is recorded.
T9 (V MAG). Test of vertical magnetic sensor; the vertical motor is running at full speed for a
predetermined time and number of triggers is recorded.
T10 (Lights). LED-module test; both lights should ignite and be lit for 30 seconds.
(first 15 sec will run the spot beam only9.
LED modules provide no feedback to to the Ebox and the test result for T10 will always show
"OK", therefore this light test must be visually verified to ensure that the LED modules light up.
T11 (OP count). Counting the number of connected operator terminals in the network.
(2.2) View Results
Displays the result of the last run diagnostics test suite.
Use the Down button to cycle through the tests results.
Use the Right button to cycle through different test result information for the selected test.
Only applicable for test “T1” and test “T10”.