6.41 Program SW3 Output Relay (RX)
1) Make sure the I-Chip is connected to the programmer.
2) Press “→” button to enter SW3 Output Relay setting.
3) Press “→” button again to enter settings.
4) Press “↑” and “↓” button to scroll and select.
5) Exit Program SW3 Output Relay by pressing the “BACK” button until the
cursor is shown next to “SW3 RLY”.
6) Press “↑” and “↓” button to scroll through other Flex 2JX settings.
Select “NORMAL” the output relay becomes momentary contact.
Select “NORMAL+S” the output relay becomes momentary contact. Must press the green
START button together to work.
Select receiver “TOGGLE” the output relay becomes toggled contact.
Select receiver “TOGGLE&E” the output relay becomes toggled contact affected by the e-stop
command (output relay opens when e-stop button is pressed).
Select “PITCH” SW3 button becomes the “Pitch” function in Pitch & Catch Operation.
Select “PITCH&E” SW3 button becomes the “Pitch” function in Pitch & Catch Operation. When
Pitch command is initiated the receiver mains are disconnected.
Select “STOP” SW3 button becomes an auxiliary e-stop function. Press to disconnect the
receiver mains and press START button to reconnect the receiver mains.
Important note 1: When one of the above is selected make sure the same SW3 button function
on transmitter is set to “NORMAL”.
Important note 2: When select Pitch & Catch function make sure you set the spare transmitter
to the next channel up and the receiver channel scanning to “02”.
Select ABUS (reversed logic A/B switching) all contacts are reversed when all pushbuttons,
rocker switches and rotary switches are set to A/A+B/B function.