ELECTRICITY
140
80
547379EN
80 (08/03/2017)
Led Message Message Description and
Investigations
Variable Speed
Controller
Hour meter Calibrator Comments
3 Flashs
MOSFET
F05009 PUp Trac MOS Failure of power test when
switching on.
- Check the following points:
With the line switch (KM1) CLOSED, the voltage at terminal A” of
the variable speed controller must be equal to the battery voltage
(if no movement activated).
With the line switch (KM1) OPEN, the voltage at terminal A of the
variable speed controller is around 7-8 V.
1 - If one of the two points above is correct, the problem originates
outside the variable speed controller. In this case, perform the following
checks (list not exhaustive):
• No negative voltage on the chassis.
The electric pump must be isolated from the chassis.
The electrical power harnesses must not be in short circuit.
2 - If any of the points described above is not proven, the
problem originates inside the variable speed controller. In this
case, perform the following checks.
2 - 1 - With the line switch (KM1) CLOSED, the voltage at terminal A”
of the variable speed controller is <3 V:
• Disconnect the travel motor cables (terminal A, S F1 & F2 on the
variable speed controller).
• Switch the variable speed controller o and on.
• Check if the problem persists.
• Disconnect connector ‘B’ of the variable speed controller logic
module, connect a wire from plug “B1” of the variable speed
controller logic module to a positive battery.
• Switch the variable speed controller o and on.
• Check the status of the LED: if the problem persists, change the
variable speed controller or otherwise check the insulation of the
variable speed controller and the switch (KM3).
2 - 2 - With the line switch (KM1) OPEN, the voltage at terminal A of
the variable speed controller is <3 V:
• Internal fault in the variable speed controller, replace it.
F05006 Mosfet s/c Failure of power test
when switching on
- Turn o the machine: if the problem persists, repeat the procedure
described above
4 Flashs
SWITCH OPEN
OR CLOSED
F05008 PUp Trac Weld Line switch (KM1)
“CLOSED” (stuck or welded) when
switched on: the variable speed
controller measures a voltage on
terminal A” 2 volts less than the
batterys rated voltage.
- Check if the line switch (KM1) is OPEN when the power supply is cut:
• KM1 OPEN: variable speed controller OK.
• KM1 CLOSED: switch stuck, check the switch, check its power
supply and replace if necessary.
- Check that there is a delay of 2 seconds between switching on and
the closure of the line switch (KM1).
• DELAY = 2s: variable speed controller OK.
• Delay ≠ 2s: variable speed controller defective, driver of LINE
switch out of service.
- Check the power cables.
F05020 Line Cont O/C Line switch (KM1)
“OPEN”: the variable speed
controller measures a voltage on
terminal A” 3 volts less than the
batterys rated voltage.
- Check:
The mechanical condition of the switch.
The coil of the switch.
The control of the switch coil.
The power and auxiliary fuses.
The wiring of the motors.
- Check output B8 of the variable speed controller logic module, the
signal is negative, if this is not the case, the line switch driver is out of
service: change the variable speed controller.
F05021 Coil s/c (std) Digital output in short circuit on
the E/S module: BASE
- Check:
• The wiring.
The elements controlled by the module.