User’s Manual Page 39 of 56
NOTE:-
The retransmission output type is jumper selectable. Thus if current type or
voltage type output, will be decided by the position of the jumper.
No need to feed input while calibrating Rx. o/p. just make the value in
calibration mode equal to the displayed value.
Example:How to change Input Type?
RT.1.Z
(rt.1.z)
Retransmission-1
ZERO
Calibration Zero for
Retransmission Output-1
(SV Display : If voltage: 0.000
If Current: 4.000)
-
Device
Supports
Retransmission
Output
RT.1.S
(rt.1.s)
Retransmission-1
SPAN
Calibration Span for
Retransmission Output-1
(SV Display : If voltage: 8.000
If Current: 20.00)
-
Device
Supports
Retransmission
Output
RT.2.Z
(rt.2.Z)
Retransmission-2
ZERO
Calibration Zero for
Retransmission Output 2
(SV Display : If voltage: 0.000
If Current: 4.000)
-
Device
Supports Dual
Retransmission
Output
RT.2.S
(rt.2.s)
Retransmission-2
SPAN
Calibration Span for
Retransmission Output-2
(SV Display : If voltage: 8.000
If Current: 20.00)
-
Device
Supports
Dual
Retransmission
Output