6.4 CONFIGURATION MODE
1 : DIR (Direct)
MR
(mr)
Manual
Reset
Adjust Manual Reset Value
It is used to shift P Band for critical
Controlling situations. (Applicable only if
Control O/P is “P”)
-(PB/2) to +(PB/2)
EX. If PB = 50, SP = 100, O.DIR = REV
MR = 0MR = 25
PV
% POWER
PV
%POWER
<= 75
100 %
<= 100
100 %
100
50 %
125
50 %
>= 125
0 %
>= 150
0 %
0
Control Type is P
ALPH
(alpH)
Sampling
Rate
Adjust Sampling Rate
Its acts like Derivative Factor. It is used to
decrease effect of D term in PID output
for some critical operating condition
0.01 to 1.00
1.00
Control Type is PID
SMP
(smp)
Sampling
Period
Set Sampling Period for Derivative Term
200 / 500 / 1
0 : 200 ms
1 : 500 ms
2 : 1 sec
200
Control Type is PID
RAMP
((Ramp))
Ramp Rate
type
none/min.r/hr.r
0:none
1:min.r
2:hr.r
None
Not available for
Output type OnOFF
Rmp.R
((rmp.r))
Ramp rate
value
0.1 to 999.9 Degree per minutes or hour
0.1
Not available for
Output type OnOFF
SOK.R
(SOK.R)
Soak rate
1 to 9999 minutes
100
Not available for
Output type OnOFF
SOK.T
(SOK.T)
Soak type
s.hod/s.rst
0:s.hod
1:s.rst
s.rst
Not available for
Output type OnOFF
CONFIGURATION PARAMETERS
Parameter
(PV display)
Setting Name & Description
Default
Value
Show if Only
Symbol
Name
INPT
(inpt)
INPUT Type
Set PV Input Type
tC e / tC j / tC K / tC t / tC b /
tC r / tC s / rtd.1 / rtd/ 0-5v / 1-
5v/0-10
TC
E