6.4 CONFIGURATION MODE
Adjust Manual Reset Value
It is used to shift P Band for critical
Controlling situations. (Applicable only if
Control O/P is “P”)
-(PB/2) to +(PB/2)
EX. If PB = 50, SP = 100, O.DIR = REV
MR = 0MR = 25
Adjust Sampling Rate
Its acts like Derivative Factor. It is used to
decrease effect of D term in PID output
for some critical operating condition
0.01 to 1.00
Set Sampling Period for Derivative Term
200 / 500 / 1
0 : 200 ms
1 : 500 ms
2 : 1 sec
none/min.r/hr.r
0:none
1:min.r
2:hr.r
Not available for
Output type OnOFF
0.1 to 999.9 Degree per minutes or hour
Not available for
Output type OnOFF
Not available for
Output type OnOFF
s.hod/s.rst
0:s.hod
1:s.rst
Not available for
Output type OnOFF
Setting Name & Description
Set PV Input Type
tC e / tC j / tC K / tC t / tC b /
tC r / tC s / rtd.1 / rtd/ 0-5v / 1-
5v/0-10