Model: LC5296-XP-AT / LC5296-XP/LC5296-XP-I
Doc. Ref. no. :- m61D/om/101
Issue no. 17
User’s Manual Page 25 of 56
Value
Input Type
Range
0
TC E
-200 to 1000 °C
1
TC J
-200 to 1200 °C
2
TC K
-200 to 1372 °C
3
TC T
-100 to 400 °C
4
TC B
450 to 1800 °C
5
TC R
0 to 1768 °C
6
TC S
0 to 1768 °C
7
RTD.1
-199.9 to 850.0 °C
8
RTD
-200 to 850 °C
9
0-5 V / 0-20
mA*
-1999 to 1999
10
1-5 V / 4-20
mA*
11
0-10V
*Use external 250ohms,0.1% for current
input
ZERO
(zero)
Zero
Automatically change to the Input Lower
Range with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input
Range & less the SPAN Value.
-200
(If
TC
E)
SPAN
(span)
Span
Automatically change to the Input Higher
Range with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input
Range & greater the ZERO Value.
1000
(If
TC
E)
OFST
(ofst)
offset
Offset Value
Input type
range
RTD/
Thermocouple
-100.0 to +100.0
Linear
-1000 to +1000
0.0
FLTR
(fltr)
Filter
Filter for PV Input
no / yes
0 : NO
1 : YES
YES
TSP1
(tsp1)
Type of Set Point
Set Type of Set Point
l-on / H-on
0 : L-ON (Lower ON)
1 : H-ON (Higher ON)
Refer ON-OFF Control on Page:40
L-
ON
Control Type is
ON-OFF.
(Not available for
Linear O/P)
OPES
(opes)
OPEN Sensor
Status
Set Control O/P & Retransmission state
when Input OPEN condition.
down / up
0 : DOWN
1 : UP
UP
RD 1
(rd 1)
Relay Delay
(For Relay-1)
Relay Delay is amount of time (in sec),
that Relay will wait before getting ON
after the ON condition occurs.
1
Control Type is
ON-OFF