Setup
Connections
EPOS4 50/5 Hardware Reference
3-20 CCMC  |  2023-07  |  rel11726
  
Table 3-12 Power supply requirements
1) Use the formula below to calculate the required voltage under load.
2) Choose a power supply according to the calculated voltage. Thereby consider:
a) During braking of the load, the power supply must be capable of buffering the recovered 
kinetic energy (for example, in a capacitor).
b) If you are using an electronically stabilized power supply, make sure that the overcurrent pro-
tection circuit is configured inoperative within the operating range.
The formula already takes the following into account:
• Maximum PWM duty cycle of 90%
• Controller’s max. voltage drop of 1 V @ 5 A
KNOWN VALUES:
• Operating torque M [mNm]
• Operating speed n [rpm]
• Nominal motor voltage U
N
 [Volt]
• Motor no-load speed at U
N
; n
O
 [rpm]
• Speed/torque gradient of the motor n/M [rpm/mNm]
SOUGHT VALUE:
• Supply voltage +V
CC
 [Volt]
SOLUTION:
Power supply requirements
Output voltage
+V
CC
 10…50 VDC
Absolute output voltage min. 8 VDC; max. 56 VDC
Output current
Depending on load 
• continuous max. 5 A
• short-time (acceleration, <15 s) max. 15 A
V
CC
U
N
n
O
-------
n
n
M
---------
M+
 
 
1
0.9
-------
  1 V +