Section 9: Entry and Exit Delay
Upon arming, the panel will begin the Exit Delay. If the ’Exit Delay Aud’ option is enabled, the keypad will beep every second until the exit
delay expires (see
9.2 ”Entry and Exit Delay Options’). The keypad will beep rapidly for the last 10 seconds of the exit delay to warn the user that
the system is about to arm.
Upon entry, if a Delay type zone is violated, the panel will begin an Entry Delay. The keypad will emit a steady tone. The keypad will pulse the
sounder during the last 10 seconds of the entry delay to warn the user that the system is about to go into alarm.
You can turn off the entry and/or exit delay tones at each keypad. See 6.3 ”Keypad Toggle Options’.
9.1 Entry and Exit Delay Times
Ref #: [0100XX02] where XX = Partition 01-08
The entry and exit delay times are programmed for each partition.
These times will program the length of each delay. Entry Delay,
Exit Delay, Auxiliary Entry Delay and Auxiliary Exit Delay.
Three digits are required for each entry. The times are program
-
mable from 000 to 255 seconds. The four partition times are as
follows:
Entry Delay - The entry delay will begin when a delay type
zone is violated (Default = 30 seconds).
Exit Delay - The exit delay will begin when a valid access
code is entered to arm the partition (Default = 120 seconds).
Auxiliary Entry Delay - This entry delay will begin when an
Auxiliary Delay zone is violated. This delay time must be
greater than the standard Entry Delay (Default = 45 seconds).
Auxiliary Exit Delay - This exit delay is for Auxiliary Delay
zones. This delay time must be greater than the standard Exit
Delay (Default = 120 seconds).
9.2 Entry and Exit Delay Options
Ref # [0100XX01] where XX = Partition 01-08
The following exit and entry delay options will determine how the
delays will sound. These options are programmed by partition.
Exit Delay Aud - If enabled, the keypad will beep during the
exit delay (once per second; twice per second during the last 10
seconds of the delay). If disabled, the keypad will be silent
during the exit delay (default=No).
Exit Delay Sqk - If enabled, the burg bell outputs will acti-
vate during the exit delay (once per second; twice per second
during the last 10 seconds of the delay). If disabled, the out
-
puts will be silent during the exit delay.
Entry Urgency - If enabled, the keypad will beep three times
every second during the last 10 seconds of the entry delay
(default=No).
Entry Squawk - If enabled, the burg bell outputs will sound
during the entry delay (once per second; twice per second
during the last 10 seconds of the delay). If disabled, the out
-
puts will be silent during the entry delay (default=No).
Exit Del. Term. - If enabled, the exit delay will reduce to five
seconds if a Standard Delay zone is opened and closed during
the delay period. The bell squawk and keypad notification
will cease upon the restoral of the delay zone. At the end of
the delay, the partition will be armed (default=No).
NOTE: The exit delay termination time will be extended to eight
seconds for systems with AML loops (over 32 detectors).
Spcl Alm Entry - If enabled, the panel will sound an alternate
entry delay if an alarm memory is present: The keypad sound
-
ers will pulse to indicate an alarm in memory. If disabled, the
panel will sound the normal entry delay, even if an alarm has
occurred during the armed period (default=Yes).
Exit Tbl Beep - If enabled, when the system is armed with
any trouble present, the keypad will sound a series of 12
beeps before the exit delay begins. If disabled, there will be
no warning beeps when arming to indicate a trouble condition
(default=No).
NOTE: If AC Trouble displayed is disabled the annunciation will not
occur for AC Trouble.
Push to Set - If a Push to Set zone is assigned to the partition
the exit delay will not be completed until the Push to Set zone
is tripped.
Extended Exit Delay - If the exit delay is programmed for
255 seconds then the exit delay will count down normally. It
will not expire until a delay zone assigned to the partition is
opened and closed.
Note that the exit delay termination feature must be enabled
and a standard delay zone must be assigned to the partition.
NOTE: Do not use this feature with the PC4820 Door Shunt feature.