44
Partition Toggle
For the partitions that are to have the openings or closings sup-
pressed, toggle the option to [Y]
NOTE: Regardless of opening suppression, when a partition is dis-
armed with alarms in memory, the opening and opening after alarm
reporting code will be reported, if programmed.
14.4 Arming/Disarming Schedules
Ref #: [001003]
Arming/disarming schedules are used to auto arm or auto disarm
partition(s) according to the selected date schedule. There are 50
Arm/Disarm schedules.
The following options are programmable for each Arm/Disarm
schedule:
Date Schedule
Enter the two digit number of the Date schedule that will be used
to auto arm/disarm.
Enter Schedule [02]-[99]. Do not use schedules 00 or 01. If these
schedules are used, the arm/disarm schedule will never activate.
Partition Toggle
Toggle the option to [Y] for the partitions that are to auto arm or
auto disarm.
Programming Date Schedule Intervals for Auto Arm/Disarm:
1. Program the time to auto arm or auto disarm as the Start time
for an interval. Program the End time as one minute after the
Start time. For example, to auto arm or auto disarm at 8 a.m.,
program the Start time as 0800 and the End time as 0801.
2. Select [Y] for the days of the week the partitions will auto
arm or auto disarm.
3. If the panel is not supposed to auto arm or auto disarm on cer-
tain days, select [Y] for any Holiday Group the schedule is to
follow.
4. Finally, toggle the Auto Arm or Auto Disarm toggle option,
depending on which function the panel should perform.
NOTE: Each interval can be used for either auto-arming or auto-dis-
arming, but not both.
In order for an arming/disarming schedule to function on a parti-
tion, the following toggle options must be enabled:
• A Date schedule must be programmed with auto-arm or auto-
disarm enabled.
• Partition toggle option ’Auto-Arm /Disarm’ must be enabled.
• User function toggle option ’Auto-Arm’ must be enabled.
This option has no effect on the ’Scheduled Disarm’ toggle
option. To disable a scheduled disarm, only ’Scheduled Dis
-
arm’ has to be disabled.
• User function toggle option ’Scheduled Arm’ or ’Scheduled
Disarm’ must be enabled.
14.5 Scheduled AMS-220/220T Smoke Detector Test
AML smoke detectors continuously monitor themselves for low
sensitivity and will report this condition as a device trouble. In
addition, this test can be conducted automatically on a pro
-
grammed schedule.
There are 50 smoke test schedules. Each smoke test schedule is
assigned a date schedule. To schedule the AML smoke detector
test, perform the following:
1. Enter reference number [001402] and press [*].
2. The keypad display will read ’Select Entry # / Enter 01-50’.
Use the arrow (< >) keys to select which Smoke Test schedule
is to be programmed and press [*}.
2. The keypad display will read ’Enter Sch.# / Enter 00-99’.
Enter the date schedule you have programmed for the smoke
test (valid entries are 02-99). The default date schedule for
each smoke test schedule is 01 (disabled).
3. The keypad display will read ’Select Toggle Partition X’. Use
the arrow (< >) keys to scroll through each partition and press
the [*] key to toggle them on (Y) or off (N). This will activate
the smoke test at the programmed time for only the selected
partitions. By default, no partition is selected (N).
When programming a date schedule, program the time to perform
the AML smoke test as the Start time for an interval. Program the
end time as one minute after the start time. For example, to per
-
form a smoke test at 8 a.m., program the Start time as 0800 and
the End time as 0801.
NOTE: A different schedule must be programmed for each partition.
Each test must be programmed to occur at least 10 minutes apart.
14.6 CTT Schedule
Ref#: [001004]
CTT Schedules are to be used with the CTT duration timer (see
section 8.3). CTT schedules are used to control the time period in
which the Close Time Timer will be activated. There are 50 CTT
Schedules.
Date Schedule entry - enter the two-digit date schedule that will
correspond to the CTT time. (Section 14.1)
Partition Toggle - press the corresponding partition number (1-8)
to 'turn on' the partition that will follow the schedule.
NOTE: CTT Schedule must not be used with UL Listed Installations.
14.7 Seismic Schedule
Ref#: [001005]
Seismic schedules are used to control the time period in which
zones defined as seismic zones will be tested. There are 50 Seis
-
mic Schedules.
Date Schedule entry - enter the two-digit date schedule that will
correspond to the time of the test.
Partition Toggle - press the corresponding partition number (1-8)
to 'turn on' the partition that will follow the schedule.
**Not UL Listed