62
Hardware Requirements
A UL Listed fire alarm installation must include at least the fol-
lowing:
PC4020CF & PC4050CR control unit
PC4701 Fire Module (dual dialer) or
Skyroute Max (cellemetry back-up) or
T-Link (TCP/IP Communicator)
When using T-Link it shall communicate to Sur-Gard MLR-
IP receiver
At least one keypad LCD4520 or LCD4521 which must be
located near the control panel
PC4702BP Bell Module (for local annunciation)
Notice on page 75 must be permanently located close to this
keypad
UL Listed input and output devices as required (not supplied)
Batteries of sufficient capacity or PS4350 with batteries to
provide 24 hours of standby supervision followed by five
minutes of alarm notification for central monitoring station
use.
PS4350 with batteries to provide 60 hours of standby supervi-
sion followed by 5 minutes of alarm notification for remote
station supervision.
Programming Requirements
Ensure that the hardware has been installed and connected cor-
rectly before attempting to program.
If the system is to report to a monitoring station, the information
listed below must be programmed. Instructions for programming
can be found in the PC4020 Installation Manual, Section 12
“Communications Programming.”
Phone Number 1: The number of the monitoring station.
System ID Code: Identifies the system to the monitoring sta-
tion.
Partition ID Code: Identifies the partition to the monitoring
station.
Reporting Codes:
2-Wire smoke alarm circuit alarm and restoration
2-Wire smoke alarm circuit trouble and trouble restoration
Waterflow alarm circuit alarm and restoration
Waterflow alarm circuit trouble and trouble restoration
System ground fault alarm and restoration
Battery trouble and trouble restoration
AC line trouble and trouble restoration
Main bell trouble and trouble restoration
Main AUX supply trouble and trouble restoration
TLM (telephone line monitor) failure and restoration (line
1)
TLM failure and restoration (line 2)
Periodic test transmission
Periodic test transmission UL
[F] key alarm and restoration
IMPORTANT NOTE: All of the above reporting codes have been
default programmed to [99]. These codes will be sent to the moni
-
toring station unless they are reprogrammed. Ensure that all of the
above codes are reprogrammed with values acceptable for the
reporting format and indications required by the monitoring station.
21.3 ULC Listing Requirements
For ULC Installations, refer to the ULC Wiring Diagram (part
#18005347) and the ULC Installation Information Sheet (part
#29002157).
When the control unit is mounted on the exterior of a vault, safe
or stockroom the enclosure shall be protected by installing inside
the following ULC listed assault attack sensors:
Sentrol 5402
Sentrol 5422