Section 21: Listing Requirements
21.1 UL Listed Commercial Burglary and Residential
Burglary Installations
The installation requirements listed below must be met for the fol-
lowing grades of service.
Grade AA Central Station and Police Connect
The installation must use T-Link module which communicates
over LAN/WAN to the Sur-Gard MLR-IP receiver. Polling time
must be 90 seconds. Compromise detection time must be 6 min
-
utes.
Grade A Local
The installation must have a bell UL Listed for mercantile local
alarms (AMSECO MBL10B).
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure (UL
Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
Grade B Central Station and Grade A Police Connect
The installation must have a bell UL Listed for mercantile local
alarms (AMSECO MBL10B).
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure (UL
Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
Grade C Central Station
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure (UL
Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
All Commercial Installations
The entry delay must not exceed 60 seconds
The exit delay must not exceed 60 seconds.
The minimum bell cutoff time is 15 minutes.
Residential Installations
The entry delay must not exceed 45 seconds
The exit delay must not exceed 60 seconds.
The minimum bell cut-off time is 4 minutes.
Programming
The notes in the programming sections describing the system con-
figurations for UL Listed installations must be implemented.
Control of the Protected Premises
In order to have a UL Certificated system the protected area is to
be under the responsibility of one ownership and management
(i.e. one business under one name). This may be a group of build
-
ings attached or unattached with different addresses but under the
responsibility of someone having mutual interest. The person of
mutual interest is not the alarm installing company.
Bell Location
The alarm sounding device (bell) must be located where it can be
heard by the person or persons responsible for maintaining the
security system during the daily arming cycle.
Protection of the Control Unit
The local control and the local power supply must be protected by
one of the following ways:
• The control unit and audible alarm device must be in a pro-
tected area which is armed 24 hours a day.
• Each partition shall arm the area protecting the control unit
and the audible alarm device power supply. This may require
duplicate protection armed by each partition. Access to this
protected area, without causing an alarm, will require that all
partitions be disarmed.
In all cases described above, the protected area for the control unit
must be programmed as not bypassable.
Casual Users
The installer should caution the user(s) to not give system infor-
mation to casual users (e.g. codes, bypass methods, etc. to baby-
sitters or service people). Only the One-Time Use codes should be
given to casual users.
User Information
The installer should advise the users and note in the user instruc-
tion manual:
• Service organization name and telephone number
• The programmed exit time
• The programmed entry time
21.2 Commercial Fire Alarm Installations
System Specifications
• Class B / Style B 2-Wire Smoke Detector Supervision
• Class B/ Style B Waterflow Supervision
• Notification Appliance Circuit Supervision
• Service Type: Automatic, Manual, Sprinkler Supervisory,
Waterflow
• Signaling Type: Non-coded
• Ground Fault Supervision
• Supervised Dual Telephone Lines
PC4XXX modules other than those specified have not been inves-
tigated by UL for use with commercial fire alarm systems and
cannot be used for commercial fire service.
All other modules providing burglary sevice must be provided in
a separate enclosure.
2-Wire Smoke Detector Compatibility
• Maximum loop resistance: 100 ohms
• Operating Voltage Range: 8.9 - 12.0
• Maximum Alarm Current: 80 mA
• Compatibility Identifier: FM-2
• The following 2-wire smoke detectors are compatible with
the PC4020CF/PC4701:
Manufacturer Model Base Type
DSC MN-220 None Photo
DSC MN-220T None Photo w/ heat
System Sensor 1100 None Ion
System Sensor 2100D None Photo
System Sensor 2100T None Photo w/ heat
System Sensor 2400 None Photo
System Sensor 1400 None Ion
System Sensor 1151 B401 Ion
System Sensor 2151 B401 Photo
System Sensor
1151 B110LP Ion
System Sensor
2151 B110LP Photo
System Sensor
1451 B401 Ion
System Sensor
1451 B401B Ion
DSC
FSA-210B None Photo