Command Output Labels
Ref #: [0100XX06YY] where XX = partition number (01-08),
YY = command output number (01-08)
Program command output labels in this section. All system dis-
play labels are programmed in a similar fashion. For instructions
on programming labels, see
5.4 ”Zone Programming’.
Police Output (46)
The output will activate when a Cross Zone/Police Code Alarm
reporting code is transmitted for any of the selected partitions. It
will remain active until a valid access code is entered on any of
the selected partition keypads.
Holdup (47)
The output will activate when a holdup zone on any of the
selected partitions is in alarm. It will remain active until a valid
access code is entered on any of the selected partition keypads. A
tamper or fault on a holdup zone will not activate the output.
Fire Zone Tbl. (48)
The output will activate when a fire zone is bypassed, or when a
fire zone trouble or fault condition is detected. The output will
deactivate when the zone is unbypassed or the trouble/fault is
restored.
Steady Fire (49)
The output will turn on steady upon any alarm from a Fire type
zone with the Audible zone attribute enabled.
Temporal Pattern Fire (50)
The output will follow the standard temporal pattern upon any
alarm from a Fire type zone with the Audible zone attribute
enabled. The temporal pattern is 0.5s ON, 0.5s OFF two times and
then 0.5s ON and 1.5s OFF. This pattern is repeated until the sig
-
nals are silenced.
NOTE: PC4204/PC4204CX/4216 v2.1 or higher is required for this
option.
CSFM Fire (51)
The output will follow the California State Fire Marshal pattern
upon an alarm from a Fire type zone with the Audible zone attri
-
bute enabled. The CSFM pattern is 10s ON and 5s OFF. This pat-
tern is repeated until the signals are silenced
Pulsed Fire (52)
The output will activate upon an alarm from a Fire type zone with
the Audible zone attribute enabled. The output will pulse ON for
0.5s and OFF for 0.5s. The pulsing will continue until the signals
are silenced.
Fire Strobe (53)
The output will turn on steadily upon an alarm from a Fire type
zone with the Audible zone attribute enabled. The output will
not
turn OFF upon signal silence but only on a successful Fire Reset.
Ground Fault (54)
The output will activate when the PC4020 detects a Ground Fault
trouble. The output will deactivate when the trouble is cleared.
Common Fire Tbl. (55)
The output activates when any of the following troubles is
detected by the panel. The output deactivates when the trouble is
cleared:
Any system AC or battery trouble (PC4020, PC4820, PC4204/
PC4204CX, PC4702, PC4850*, Alternate Communicator*)
Any system communicator trouble (TLM1, TLM2, FTC,
LINKS, Alternate Communicator*)
Ground Fault trouble
Bell Trouble (56)
The output will activate for a trouble (open or short) on any super-
vised system bell output (PC4020 or PC4702). The output will
deactivate when the trouble is cleared.
AC Status (57)
The output will be active when AC is present on the PC4020 as
well as all enrolled modules (PC4204/PC4204CX, PC4820,
PC4702, PC4850*, Alternate Communicator*). The output will
deactivate when an AC Fail trouble condition is generated. This
output will follow the ’AC Fail Delay,’ if programmed (see
10.9
”Transmission Delay’).
Partition Status Alarm Memory (58)
The output will activate when any of the selected partitions are
armed. It will deactivate when all selected partitions are disarmed.
If an alarm, tamper or fault occurs on any of the assigned parti
-
tions, the output will flash for the remainder of the armed period.
If the partition is disarmed, the output will flash until the alarm is
acknowledged, or the bell time-out period expires.
Card Used PGM Type (59)
When this output type is programmed, the panel will prompt the
installer to enter the user number that this output will activate for.
The output will be active for the amount of time programmed in
the Pulse Timer whenever an Access Granted event is sent for that
user. If programmed for 000 the output will toggle On/Off
depending on its initial state.
Battery Test Output (60)
Whenever partition one is disarmed the panel will perform a 30-
second battery test. During this battery test any PGM output pro
-
grammed as Battery Test will activate for the duration of the bat-
tery test. The output is intended to be used to switch a load onto
the battery circuit.
Seismic Test (61)
This output type will activate for 15 seconds upon disarm-ing or
when a seismic schedule becomes active. The seis-mic test will be
active for forty seconds. The zones defined as seismic zones will
be tested for an 'open condition' during the first twenty seconds
and tested for a 'restore' during the last twenty seconds. This out
-
put can be used on a sys-tem that has Seismic Zone types defined.
This is only a testing output that will trigger the zone into alarm.
The panel will ensure that all zones that are programmed as a
Seismic Sensor have gone into alarm.
The Seismic Sensor Output will then be deactivated and the
panel will wait 10 seconds allowing the Seismic Sensors to
restore.
The panel will then ensure that all zones that are pro-
grammed as a Seismic Sensor have restored.
If all Seismic Sensor zones have properly gone into alarm and
restored, the ready light will be activated and no fault will be
initiated.
If any of the Seismic Sensor zones fail to go into alarm or to
restore a "Zone Fault" event will be transmitted and the event
number will be logged to the event buffer, for each zone that
failed.
If the Force Arming bit has been set for all Seismic Sen-sors
that have failed, the partition shall allow arming fol-lowing
the normal force arming procedure.
If the Force Arming bit has not been set for all Seismic Sensors
that have failed, the ready light will be deacti-vated (if active),
an error tone will sound, and the corre-sponding zone will indi
-
cate as "Open" in the menu.
Global seismic zones will not be supported.
If a Seismic zone fails the Seismic Sensor test the zone will
indicate, as "Open" and the partition will be unable to arm.
(Unless the force arm bit is enabled).
The panel will show the zone as open and a trouble will be
displayed in * 2 menu called 'Seismic Trouble'
The trouble can only be cleared by entering\exiting installer's
mode.
11.4 Output Pulse Times
Ref #: [000706XX] where XX = pulse time type 00-03
This section will allow you to select the amount of time the PGM
output will remain active after being triggered. Valid entries are
from 000 to 255 seconds. The available pulse times are listed
below:
Kissoff Pulse (00)
Any output programmed for ’Kissoff’ can be active from 000 to
255 seconds. The default setting is 003 seconds.