Fire Configuration 2 (Recommended)
• Assign ALL fire zones to ALL active partitions in the system.
Do not program fire zones as ‘silent’.
• PC4702 Bell zones automatically respond to any fire zone in
the system and can be assigned to any partition.
• Zones on the PC4701 module are always global and do not
require partition assignment.
• One or more fire keypads may be located on any partition.
Operation
On alarm, the fire auto-scroll display will show on all partition
keypads and on all global keypads.
Fire alarm silence and fire system reset may be done directly on
any partition keypad. To silence from a global keypad requires
that the global keypad be loaned to one of the partitions.
NOTE: Assign command output 2 (sensor reset) to all partitions.