76
Figure 50: CT Ratio Test Connection Diagram - Non Concurrent
12. Check all connections to ensure correctness
13. Hit Blue Play button.
14. A dialog will appear requesting how much Voltage to apply to the CT during
the ratio test
15. Enter a voltage 1V and 300V that is less than the knee point of the CT
16. Hit Blue Play button to begin test.
17. The Ratio test will begin.
X Voltage (V): The MRCT displays the real time voltage readings of the secondary X winding
while the test is in progress.