Note:
Only the following function No. will be shown in the quick menu: 0, 1, 3, 4, 5, 6, 7, 8, 9, 15, 16.
Fig. 6-39 Output terminal enabled status setting
This function code defines the positive/negative logic of the output terminal.
Positive logic: enabled when the output terminal is connected to the corresponding common end,
disabled when the terminal is disconnected;
Negative logic: disabled when the output terminal is connected to the corresponding common end,
enabled when the terminal is disconnected;
This function code defines the time delay from the state change of relay RO1 to its output change.
This function code is used to detect the deviation between the output frequency and the set frequency. If
the output terminal function is set as “1: Frequency arrival signal”, when the deviation between the output
frequency and the set frequency is within the range set by this function code, the relevant indication
signal will be output, as shown in Fig. 6-40.
1/2
detecting range
Time
Time
Y
Preset
freq.
Output
Fig. 6-40 Schematic diagram for frequency arrival signal output
P09.25~P09.26 are the complementary definitions of the No.3 function in P09.21, and P09.27~P09.28
are the complementary definitions of the No.4 function in P09.21. They have the same use method. The
following will take P09.25~P09.26 for example.
FDT 2 level lower limit 0.00~P02.17 (24.00Hz)P09.28
FDT 2 level upper limit P09.28~P09.26 (25.00)P09.27
FDT 1 level lower limit 0.00~P09.25 (49.00Hz)P09.26
FDT 1 level upper limit P09.26~P02.16 (50.00)P09.25
Frequency arrival (FAR) detection width 0.00~3000.00Hz(2.50Hz)P09.24
Relay RO1 output delay 0.1~10.0s (0.1s)P09.23
Output terminal enabled status setting 0~F (0)P09.22