182
When the output frequency exceeds the set frequency P09.25 (FDT1 level upper limit), the relevant
indication signal will be output, until the output frequency is reduced to lower than certain frequency of the
FDT1 level (FDT1 level lower limit), As shown in Fig. 6-41.
Fig. 6-41 Schematic diagram for frequency level detection
Table 6-13 Function definition of the multi-functional digital output
Item Function Indication range
0 No function None
1 Output frequency 0~Maximum output frequency
2 Set frequency 0~Maximum output frequency
3 Output current Iei 0 ~ 200% of the rated current of the drive
4 Output current Iem 0~200% of the rated current of the motor
5 Output torque 0~300% of the rated torque of the motor
6 Output torque current 0~300% of the torque current
7
Rotating speed of motor (V/F
control disabled)
0~Maximum rotating speed
8 Output voltage 0~150% of the rated voltage of the drive
9 AI1 voltage -10V~10V/4~20mA
10 AI2 voltage -10V~10V/4~20mA
11 AI3 voltage -10V~10V
12 Output power 0~200% of the rated power
13 Electric torque limit value 0~300% of the rated torque of the motor
14 Braking torque limit value 0~300% of the rated torque of the motor
15 Torque offset 0~300% of the rated torque of the motor
16 Torque reference 0~300% of the rated torque of the motor
17
HOST device expansion
function 1
0~65535
18
Encoder frequency division
output
Reserved
19 Percentage of bus card 0~65535
The DO pulse frequency output: 0 to maximum output pulse frequency.
The linear correspondence relationship between the DO output and the indication range is as shown in
Table 6-13.
Maximum output pulse frequency 0.1~50.0kHz (10.0 kHz)P09.30
DO terminal output 0~19 (0)P09.29