84
P06.24
Under-torqu
e detection
value
Under-torque
detection
value
0~300.0%
SVC: Rated torque of equivalent
motor
V/F: Rated current of equivalent
motor
0.1% 0%
×× ×
P06.25
Under-torqu
e detection
time
Under-torque
detection
time
0.0~10.0s 0.1 0.0 × × ×
Group P07: VF control parameters
P07.00
Motor 1 V/F
curve
setting
Motor 1 V/F
curve setting
0: User-customized V/F curve
1: Constant torque feature 1
2: Constant torque feature 2
3: Constant torque feature 3
4: Reserved
5: Decrease torque feature 1
6: Decrease torque feature 2
7: Decrease torque feature 3
8: Decrease torque feature 4
9: High starting torque feature 1
10: High starting torque feature 2
11: High starting torque feature 3
12: High starting torque feature 4
13: Reserved
14: Reserved
15: Reserved
16: Reserved
17: 2 times power curve
18: 1.7 times power curve
19: 1.2 times power curve
1 0 × √ ×
P07.01
Motor 1 V/F
frequency 3
Motor 1 V/F
frequency 3
P07.03~P03.03 0.01Hz 0.00Hz × √ ×
P07.02
Motor 1 V/F
voltage 3
Motor 1 V/F
voltage 3
P07.04~100.0% 0.1% 0.0% × √ ×
P07.03
Motor 1 V/F
frequency 2
Motor 1 V/F
frequency 2
P07.05 ~P07.01 0.01Hz 0.00Hz × √ ×
P07.04
Motor 1 V/F
voltage 2
Motor 1 V/F
voltage 2
P07.06~P07.02 0.1% 0.0% × √ ×
P07.05
Motor 1 V/F
frequency 1
Motor 1 V/F
frequency 1
0.00~P07.03 0.01Hz 0.00Hz × √ ×
P07.06
Motor 1 V/F
voltage 1
Motor 1 V/F
voltage 1
0~P07.04 0.1% 0.0% × √ ×
P07.07
Motor 1
torque
increase
Motor 1
torque
increase
0.0%~30.0% 0.1% 0.0% × √ ○
P07.08
Motor 1 Motor 1
0.0%~50.0% (corresponds to
0.1% 10.0% × √ ○