93
P09.22
Output
terminal
enabled
status
setting
Output
terminal
enabled
status
Binary setting:
0: Enabled upon connection
1: Enabled upon disconnection
Unit place of LED:
BIT0~BIT3:Y1Y2RO1RO2
1 0 ×
P09.23
Relay RO1
output delay
RO1 output
delay
0.1~10.0s 0.1s 0.1 ×
P09.24
Frequency
arrival
(FAR)
detection wi
dth
Frequency
arrival
detection wid
th
0.00~3000.00Hz 0.01Hz 2.50Hz ×
P09.25
FDT 1 level
upper limit
FDT 1 level
upper limit
P09.26~ P02.16 0.01Hz 50.00Hz ×
P09.26
FDT 1 level
lower limit
FDT 1 level
lower limit
0.00~ P09.25 0.01Hz 49.00Hz ×
P09.27
FDT 2 level
upper limit
FDT 2 level
upper limit
P09.28~ P02.16 0.01Hz 25.00Hz ×
P09.28
FDT 2 level
lower limit
FDT 2 level
lower limit
0.00~ P09.27 0.01Hz 24.00Hz ×
P09.29
DO terminal
output
Digital output
0: No function
1: Output frequency
2: Set frequency (0~Maximum
output frequency)
3: Output current I
ei
(0~2 * I
ei
)
4: Output current I
em
(0~2 * I
em
)
5: Output torque (0~3 * T
em
)
6: Output torque current
(0~3*I
tem
)
7: Motor rotating speed
(0~Maximum output frequency)
8: Output voltage (0~1.5 * V
e
)
9: AI1-10~10V/4~20mA
10: AI2-10~10V/4~20mA
11: AI3 -10~10V
12: Output power (0~2*P
e
)
13: Electric torque limit value
(0~3T
em
)
14: Braking torque limit value
(0~3Tem)
15: Torque offset (0~3T
em
)
16: Torque reference (0~3T
em
)
17: Percentage of host device
(0~65535)
18: Reserved
1 0