6. Operating | 6.2 - Configuration and adjustment via the keypad | 130
6.2.12.1 Adapting the analog output
The output current can be adjusted in small ranges. This is required if small
deviations from the nominal value occur in a connected PLC.
1. Press and hold for 2–3 seconds.
SEtuP appears on the display.
2. Press "OK".
Cd 000 appears on the display (Cd flashes).
3. Press (5×) to select Ao 050.
4. Press / and / to select Ao 057.
CAL-04 appears on the display.
5. Press "OK".
04000 appears on the display (the last digit flashes).
6. Press / and / to input the value reported by the connected
PLC for 4mA.
7. Press "OK".
Ao 058 appears on the display.
8. Press "OK".
CAL-20 appears on the display.
9. Press "OK".
20000 appears on the display (the last digit flashes).
10. Press / and / to input the value reported by the connected
PLC for 20mA.
11. Press "Exit".
12. Save the changes.