5.7.1 Enabling or Disabling the Positive Alarm Sequence
Enabling or Disabling the Positive Alarm Sequence is done using the numeric keypad. For
more information on how to use the Numeric Keypad see 6.2.1 Numeric Keypad and Cursor
Buttons on page 49.
How to enable or disable the Positive Alarm Sequence
1. From the Keypad of the FACP press M to enter the Menu.
2. Using the Up and Down cursor buttons, scroll to Operation.
3. Press Enter.
4. In the Operation Menu scroll to Positive Alarm.
5. Press Enter.
6. You will now see the current status of the Positive Alarm Sequence and will be
prompted to change status.
Figure 8 Enabling the Positive Alarm Sequence
7. To change the status press Enter.
8. To exit without changing the status press Cancel.
How to enable the Positive Alarm Sequence in the MGC-3000 Configurator
In the Job Details window, check the Positive Alarm Sequence box.
This option only applies to alarm input devices with the PA flag (F2) set.
5.8 Remote Annunciator Operation
The FX-400 Fire Alarm Control Panel supports the following types of annunciators
• RAX-LCD-LITE shared display annunciator.
• RAM-3318-LCD shared display annunciator.
• Conventional LED/switch annunciators.
Both types (RAX-LCD-LITE and RAM-3318-LCD) of annunciators are connected to the panel
via the RS-485 serial link (Class B).
The maximum number of annunciators is seven (7). Configuration of the annunciators is done
via the MGC-3000 software configurator.
Note: Positive Alarm Sequence needs to be configured in the configuration job file
before it is sent to the panel. There will be no notification message advising a
change of status.
Pos Alarm disabled
Enable ? Y