5.1.5 Auto Test
Periodically each detector is commanded to return an alarm value to test its ability to alarm. If
the device fails the test, a trouble is indicated on that device. This trouble is latched until
system reset.
5.2 Configurable Input Types
Input devices and modules may be configured as one of many possible input types. Table 7
identifies the device types assignable to each input type. For device type descriptions see
sections 5.2.1 to 5.2.12.
Table 7 Configurable Input Types
Input Type
As listed in
Configurator
Description
located in
Section number
Device Types
Detectors
Dual Input Module
Mini Dual Input Module
Conventional Zone
Module
Alarm Input Alarm Input 5.2.1 XX
Latched Supervisory Latched Supv 5.2.2 XX
Building/Property Safety
Input
Building 5.2.3 XX
Non-Latching
Supervisory
Non-Latch Supv 5.2.2 XX
Priority Alarm Priority Alm 5.2.4 XX
Trouble Input Trouble Input 5.2.5 XX
Waterflow Alarm Input Waterflow 5.2.6 X
System Reset Sys Reset 5.2.7 X
Fire Drill Fire Drill 5.2.7 X
Acknowledge Ack 5.2.7 X
Total Evacuation Total Evac 5.2.7 X
Auxiliary Disconnect Aux Disc 5.2.7 X
Buzzer Silence Buzz Sil 5.2.7 X
Signal Silence Signal Silence 5.2.7 X
Acknowledge General
Alarm
Ack GA 5.2.7 X
Audible Walktest Audible Walktest 5.2.8 X
Silent Test Silent Test 5.2.9 X
Manual Day/Night Manual Day/Night X
Auto Day/Night Auto Day/Night X
Auxiliary Reset Auxiliary Reset 5.2.7 X
Verified Alarm Verified Alm 5.2.12 X