39
3. Current levels
The current levels report displays real-time device information for all eligible devices on the
target loop or for all eligible devices on all loops if you specify a target loop or select all.
Eligible devices are those present in the configuration and also those detected as present on
the real loops. You can indicate the device address to start with, but only if you indicated the
loop number as 1, 2, or 3.
Device information consists of the percent of alarm if the device is an input.
1. Enter the loop number of the desired device and press the Enter button.
The display shows the loop number, device address, the device type, device status, and
the level of alarm, in the following format:
2. Press the Up and Down cursor keys to scroll through all the devices on the loop.
3. Press the Info Button to see more information about the selected device.
4. Verify counts
The verification count report displays the number of times that the alarm verification cycle has
been initiated without causing an alarm for all verified device or circuits on the specified loop or
loops. If the count is zero, the device is not displayed.
Enter the loop number of the desired device and press the Enter button.
The report shows the loop#, device address and verify count in the following format:
Press the Up and Down cursor keys to scroll through all the devices on the loop for which the
verify count is available. If there are no verified devices on the loop the following message
appears.
If no verified devices with a non-zero counter are found on the specified loop(s), a message is
displayed to that effect.
Loop Number
Loop :__
(MIX4) Photo Det
Threshold: 192
Loop Number
Loop :__
Lp:1 Addr :001
Verify count :000
No verified devices
found