LAN
--------------- P26.14
Delay before
protection OFF with
Treturn in range:
300s
Parameter for configuring the time of deactivation of the Hot & Cold Spot function
after returning within the limits.
Visible only if Hot&Cold spot management is enabled.
LAN
--------------- P26.15
Delay bef. Protection
ON with Treturn
out of range: 060s
Parameter for configuring the time of activation of the Hot & Cold Spot function after
exceeding the limits.
Visible only if Hot&Cold spot management is enabled.
LAN
--------------- P26.16
Active Fan on Stand-by
units enable: N
--------------- P26.17
Stand-by units Active
Fan speed: 070%
Enable the Active Fan on Standby function.
Speed of the fans in units on standby.
LAN
--------------- P26.18
Active Pressure Load
enable: N
--------------- P26.19
Disable APL during
Diff.P probe alarm: N
Parameter enabling the Active Pressure Load function.
Visible only if LAN is enable and the fans are adjusted according to the air DeltaP.
Parameter for disabling fan regulation according to Active Pressure Load on units
with air differential transducer in alarm.
Visible if Active Pressure Load function is enabled.
LAN
--------------- P26.20
H&L Local Pressure
protection enable: N
Parameter for enabling the High & Low Local Pressure protection function.
Visible if Active Pressure Load function is enabled.
LAN
--------------- P26.21
Diff. for ON with High
local DeltaP: 010Pa
--------------- P26.22
Diff. for ON with Low
local DeltaP: 010Pa
Parameters for setting the threshold for independent fan control on units with above-
average floor pressures.
Parameters for setting the threshold for independent fan control on units with below-
average floor pressures.
Visible only if high & low local pressure protection function is enabled.
LAN
--------------- P26.23
Delay before
protection OFF with
local DeltaP in range:
300s
Time before return to regulation according to the average pressure on units with
local pressure within the norm.
Visible only if high & low local pressure protection function is enabled.
LAN
--------------- P26.24
Delay before
protection ON with
local DeltaP out of
range: 060s
Time before start of regulation according to local pressure on units with local
pressure outside the norm.
Visible only if high & low local pressure protection function is enabled.