--------------- P31.49
(010/510) Flood Alarm/
Flood Warning: A
Addressing of the flooding alarm/signal on digital output.
Alarm out addressing
--------------- P31.50
(520) LAN Interrupted:
A
Addressing of the LAN interrupted alarm on digital output.
Alarm out addressing
--------------- P31.94
(531) Return Temp.
Above HH Limit: A
Addressing of the hazardous high temperature alarm on digital output.
Alarm out addressing
--------------- P31.51
(530) Return Temp.
Below Min. Limit: A
--------------- P31.52
(531) Return Temp.
Above Max. Limit: A
Addressing of the low temperature alarm on digital output.
Addressing of the high temperature alarm on digital output.
Alarm out addressing
--------------- P31.53
(540) Return Humidity
Below Min. Limit: A
--------------- P31.54
(541) Return Humidity
Above Max. Limit: A
Addressing of the return humidity below minimum limit alarm on digital output.
Addressing of the return humidity above maximum limit alarm on digital output.
Alarm out addressing
--------------- P31.55
(601) EEPROM Error:
A
--------------- P31.56
(610) Maintenance
Needed: A
Addressing of the EEPROM alarm on digital output.
Addressing of the maintenance alarm on digital output.
Alarm out addressing
--------------- P31.57
(620) Faulty Fan :
A
--------------- P31.58
(630) Clogged Filters:
A
Addressing of the faulty fan alarm on digital output.
Addressing of the dirty filters alarm on digital output.
Alarm out addressing
--------------- P31.62
(323) Circuit 1 Frost
Protection Active: A
--------------- ------
Addressing of the circuit 1 frost-free function active alarm on digital output.
Alarm out addressing
--------------- P31.67
(711) BMS1 Bus
Offline: A
Addressing of the BMS1 port offline alarm on digital output.