EasyManua.ls Logo

Mitsubishi Electric MELSEC-L Series - Chapter 12 Communications Using a Fixed Buffer; Applications; Differences between the Procedure Exist and No Procedure Control Methods

Mitsubishi Electric MELSEC-L Series
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120
CHAPTER 12 COMMUNICATIONS USING A FIXED
BUFFER
This chapter describes communications using a fixed buffer.
12.1 Applications
In communications using a fixed buffer, a programmable controller can actively send data; therefore, data can be sent
from the programmable controller to the host system when an error occurs in machine equipment or some other
conditions are satisfied. A maximum of 1K word of data can be sent or received between programmable controllers or
between a programmable controller and the host system.
12.1.1 Differences between the "Procedure Exist" and "No
Procedure" control methods
There are two control methods for communications using a fixed buffer; "Procedure Exist" control method and "No
Procedure" control method. This section describes the differences between the "Procedure Exist" and "No Procedure"
control methods.
A connection with a connected device is dedicated for "No Procedure" communications using a fixed buffer. MC protocol
communications and "Procedure Exist" communications using a fixed buffer and random access buffer cannot be performed
at the same time as "No Procedure" communications using a fixed buffer.
Item
Difference
Procedure Exist No Procedure
Message format Data is sent/received in a fixed data format.
Data is sent/received in the message format of the
connected device.
A response to data receiving A response to data receiving is sent. A response to data receiving is not sent.
Data code
Communications can be performed using a
binary code or ASCII code.
Communications are performed using only a binary
code.
Data length specified using a
dedicated instruction
Specified by the number of words. Specified by the number of bytes.
Amount of application data per
communication
Maximum of 1017 words Maximum of 2046 bytes

Table of Contents

Other manuals for Mitsubishi Electric MELSEC-L Series

Related product manuals