EasyManua.ls Logo

Mitsubishi Electric MELSEC-L Series - Network Components

Mitsubishi Electric MELSEC-L Series
382 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
5.2 Network Components
This section describes the devices used for Ethernet.
An E71 determines whether to use 100BASE-TX or 10BASE-T and the full-duplex or half-duplex transmission mode
according to the hub. For connection to a hub without the automatic negotiation function, set the half-duplex mode on the
hub side.
(1) 100BASE-TX connection
To configure a system for 100BASE-TX connection, use devices that meet the IEEE 802.3 100 BASE-TX
standards.
*1 This applies when a repeater hub is used. For the number of levels that can be constructed when a switching hub is
used, consult with the manufacturer of the switching hub used.
*2 Data can be communicated with an E71 (between LJ71E71-100 modules). In addition, an E71 can be directly connected
to a GOT.
During high-speed communications (100Mbps) using 100BASE-TX connection, a communication error may occur due to
high-frequency noise from devices other than a programmable controller in a given installation environment. The following
lists countermeasures to be taken on the E71 side to avoid high-frequency noise influence.
Wiring connection
Do not bundle the cable with the main circuit or power cable or do not place it near those lines.
Put the cable in a duct.
Communication method
Use TCP/IP for data communications with connected devices.
Increase the number of retries of communications if needed.
10Mbps communications
Use a 10Mbps hub for the E71 and set the data transmission speed to 10Mbps.
Change the transmission speed of the E71 to 10Mbps using the UINI instruction. ( Page 233, Section
15.13)
Remark
Consult a network specialist for required devices.
Configuration device Description
Shielded twisted pair
cable (STP)
*2
Straight cable A Category 5 or 5e cross cable is usable.
Cross cable A Category 5 or 5e cross cable is usable.
Connector RJ45 connector
Hub 100Mbps hub
Up to two levels of cascade connection can be configured.
*1
Connected device
E71
Hub

Table of Contents