14.4.4 Differences in functions according to the remote password
check status (enabled/disabled)
The following table lists the behavior of the functions according to the remote password check status
(enabled/disabled).
Function
Remote password check setting
Disabled Enabled
Connection with MELSOFT products and a
GOT
After an initial process is completed,
communications are enabled by
establishing a connection in the
programming tool.
After the remote password is entered,
communications are enabled. The remote
password lock process is automatically
performed when the project is closed.
MC protocol
communications
User open port
After an open process is completed,
communications are enabled.
After an open process is completed,
communications are enabled from the time
that the unlock command is received until
the lock command is received.
Auto-open UDP port
After an initial process is completed,
communications are enabled.
After an initial process is completed,
communications are enabled from the time
that the unlock command is received until
the lock command is received.
Communications
using SLMP
User open port
After an open process is completed,
communications are enabled.
Use MC protocol to communicate with the
CPU module where a remote password is
set because SLMP does not have unlock
and lock commands.
Auto-open UDP port
After an initial process is completed,
communications are enabled.
Communications using the predefined protocol
After an open process is completed,
communications are enabled.
After an open process is completed,
communications are enabled.
*1
Communications using the predefined protocol
support function
After an initial process is completed,
communications are enabled by
establishing a connection in GX Works2.
After the remote password is entered,
communications are enabled. The remote
password lock process is automatically
performed when the protocol setting data
are closed.
Communications
using a fixed buffer
Procedure exists
After an open process is completed,
communications are enabled.
After an open process is completed,
communications are enabled from the time
that the unlock command is received until
the lock command is received.
No procedure
After an open process is completed,
communications are enabled.
*1
Communications using a random access buffer
After an open process is completed,
communications are enabled from the time
that the unlock command is received until
the lock command is received.
E-mail function
After an initial process is completed, data
sending and receiving are enabled.
*2
After an initial process is completed, data
sending and receiving are enabled.
*2
Web function
After an initial process is completed,
communications are enabled.
After the remote password is entered,
communications are enabled. The remote
password lock process is automatically
performed when the Web browser is
closed.
CC-Link IE Controller Network, CC-Link IE Field
Network, MELSECNET/H, and
MELSECNET/10 relay communications
After an initial process is completed,
communications are enabled.
*3
Communications using data link instructions