273
CHAPTER 16 TROUBLESHOOTING
16
16.7 Error Code List
16.7.3 Error codes stored in the buffer memory
16.7.3 Error codes stored in the buffer memory
The following table lists the error codes stored in each buffer memory area when an error occurs. For the buffer
memory areas where these error codes are stored, refer to the descriptions of the corresponding buffer memory area.
( Page 35, Section 3.5.2)
Error code Error description Action
00
H
The error details and how to troubleshoot the problem are the same as those for the end code returned to the connected
device in data communications. ( Page 268, Section 16.7.1)
02
H
0050
H
0051
H
0052
H
0054
H
0055
H
0056
H
0057
H
0058
H
0059
H
005B
H
• The CPU module and the Ethernet module cannot
communicate.
• The programmable controller CPU cannot process the
request from the connected device.
• Check the error code appended to the end code and
correct the error.
0060
H
• The communication time between the CPU module and
the Ethernet module exceeded the CPU monitoring timer
value.
• Increase the CPU monitoring timer value.
0063
H
• In communications using a fixed buffer, the remote
password of the port for the destination Ethernet module
is in the lock status.
• After unlocking the remote password using the MC
protocol, perform communications using a fixed buffer.
• Exclude ports used for communications using a fixed
buffer from the targets of the remote password check.
00A0
H
This request cannot be specified in connection with the
connected device.
• Correct the request details.
• Correct the open setting.
00A1
H
Contents of the request cannot be analyzed because the
text length or request data length is too short.
• Check and correct the text length or request data length of
the Qn header. Then send data to the Ethernet module
again.
00A2
H
This request cannot be processed. • Correct the request details and command.
3E8
H
to
4FFF
H
(Errors detected by a programmable controller CPU)
• Refer to the troubleshooting section of the user's manual
(hardware design, maintenance and inspection) for the
CPU module used, and take corrective action.
7000
H
to
7FFF
H
(Errors detected by a module such as a serial
communication module)
• Refer to a manual such as a serial communication module
user's manual, and take corrective action.
B000
H
to
BFFF
H
(Errors detected by a CC-Link module)
• Refer to the CC-Link System Master/Local Module User's
Manual, and take corrective action.
C001
H
• The IP address setting value of the E71 for the initial
process is incorrect.
• The setting value of the subnet mask field for the router
relay function is incorrect.
• Correct the IP address. Set the class to A/B/C.
• Correct the subnet mask.
C002
H
Some of the various timer setting values for the initial
process are outside the allowable range.
• Check and correct each timer setting value for the initial
process.
C003
H
The setting value of the auto-open UDP port number for
the initial process is outside the allowable range.
• Check and correct the auto-open UDP port number.