CHAPTER 16 TROUBLESHOOTING
16
16.6 Troubleshooting by Symptom
16.6.2 The E71 frequently fails to receive a message sent from the connected device.
16.6.2 The E71 frequently fails to receive a message sent from the
connected device.
The following table lists how to troubleshoot the problem when the E71 frequently fails to receive a message sent from
the connected device.
*1 Availability depends on the version of the E71. ( Page 310, Appendix 3)
If the action above does not solve the problem, perform the following tests on the E71 to check for hardware error.
Hardware test ( Page 333, Appendix 6.2)
Self-loopback test ( Page 332, Appendix 6.1)
16.6.3 A dedicated instruction is not completed.
The following table lists how to troubleshoot the problem when a dedicated instruction is not completed.
If the action above does not solve the problem, perform the following tests on the E71 to check for hardware error.
Hardware test ( Page 333, Appendix 6.2)
Self-loopback test ( Page 332, Appendix 6.1)
Check item Action
Has the error code C0C7
H
been stored in Error code/end
code (address: E5
H
) in the error log block?
There may be a heavy load on the Ethernet line due to data sending and
receiving between connected devices.
Taking action such as separating networks or decreasing the number of data
sending reduces the load on the Ethernet line.
Consult the network administrator and reduce the load on the Ethernet line.
Has 1
H
been stored in Receive buffer full detection signal
(address: 5240
H
)?
*1
Taking action such as separating networks or decreasing the number of data
sending reduces the load on the Ethernet line.
When communications using a fixed buffer is used, check whether the
BUFRCV instruction is executed. ( Page 125, Section 12.4.1)
To receive data at shorter intervals than the scan time of the CPU module
using a fixed buffer, add the normally closed contact for the completion
device of the BUFRCV instruction to the execution conditions of the
BUFRCV instruction. ( Page 153, Section 12.9.3 (2) (b))
Has the number in Received TCP packet count (address:
1B8
H
and 1B9
H
) increased?
If the packets cannot be received even though the number of received TCP
packets has increased, set the value of TCP Maximum Segment Transmission
setting area (address: 1E
H
) to 8000
H
. Then perform the initial process again.
( Page 311, Appendix 4)
Check item Action
Is the network parameter mode set to "Online"?
Set the network parameter mode to "Online".
( Page 66, Section 7.1.2) (If a dedicated instruction is executed in the
"Offline" mode, no error occurs but the instruction is not completed.)