271
CHAPTER 16 TROUBLESHOOTING
16
16.7 Error Code List
16.7.1 End codes returned to a connected device during data communications
59
H
An extension file register cannot be
specified.
Correct the device
specification.
5B
H
The CPU module and the E71 cannot
communicate.
The CPU module cannot process a
request from a connected device.
Check the error code
appended to the end
code and correct the
error.
60
H
The communication time between the
CPU module and the E71 exceeded
the CPU monitoring timer value.
Increase the CPU
monitoring timer
value.
63
H
In communications using a fixed
buffer, the remote password of the port
for the destination E71 is in the lock
status.
After unlocking the
remote password
using the MC
protocol, perform
communications
using a fixed buffer.
Exclude ports used
for communications
using a fixed buffer
from the targets of the
remote password
check.

A0
H
to
FFFF
H
The error details and how to troubleshoot the problem are the same as those for the error code stored in the buffer memory.
( Page 273, Section 16.7.3)
Error
code
Error description Action
Data communication type
MC protocol
communications
Communications
using a fixed
buffer
Communications
using a random
access buffer