276
C034
H
On the ARP table, there is no connected device with the IP
address that has been set.
Decrease the number of communication destinations.
C035
H
The existence of the connected device could not be
checked within the response monitoring timer value.
Check the operation of the connected device.
Correct the settings of the alive check.
Check if the cable is disconnected.
C036
H
Because a cable is not connected or disconnected, the
send process cannot be executed.
Check if the cable is disconnected.
Perform the loopback test to check for an error in the line.
Perform the self-diagnostics test to check for an error in
the Ethernet module.
C040
H
Not all the data could be received within the response
monitoring timer value.
Sufficient data for the data length could not be received.
The remaining part of the message divided at the
TCP/IP level could not be received within the response
monitoring timer value.
Correct the data length of the communication data.
Because there may be congestion of packets on the line,
correct the settings of the initial process.
Send the same data from the connected device again.
C041
H
There is an error in the checksum of the receive data when
TCP is used.
Correct the checksum value sent from the connected
device and send the correct value.
Check the situation of the line, such as noise, the distance
between the line and power cable, and the grounding of
each device.
C042
H
There is an error in the checksum of the receive data when
UDP is used.
Correct the checksum value sent from the connected
device and send the correct value.
Check the situation of the line, such as noise, the distance
between the line and power cable, and the grounding of
each device.
C043
H
The checksum in the header of the IP packet received is
incorrect.
Correct the checksum value sent from the connected
device and send the correct value.
Check the situation of the line, such as noise, the distance
between the line and power cable, and the grounding of
each device.
C044
H
An error packet of ICMP was received.
Check the operation of the connected device.
Check if the cable is disconnected.
C045
H
An error packet of ICMP was received.
Check the operation of the connected device.
Check if the cable is disconnected.
C046
H
An error packet of ICMP was received.
Check the operation of the connected device.
Check if the cable is disconnected.
C047
H
An error packet of ICMP was received.
Check the operation of the connected device.
Check if the cable is disconnected.
C048
H
An error packet of ICMP was received.
Check the operation of the connected device.
Check if the cable is disconnected.
C049
H
An error packet of ICMP was received.
Check the operation of the connected device.
Because there may be congestion of packets on the line,
send data after a certain period of time.
Check if the cable is disconnected.
If an alive check timeout occurs, correct the IP assembly
timer value of the connected device.
C04A
H
An error packet of ICMP was received. (An IP assembly
timeout error has occurred in the connected device.)
Check the operation of the connected device.
Because there may be congestion of packets on the line,
send data after a certain period of time.
Check if the cable is disconnected.
If an alive check timeout occurs, correct the IP assembly
timer value of the connected device.
Error code Error description Action