The communication time between the Ethernet module
and the programmable controller CPU exceeded the CPU
monitoring timer value.
Increase the CPU monitoring timer value.
Check that the programmable controller CPU is operating
normally.
Correct the network number or PC number.
If the destination is a station with a different network
number, correct the routing parameter setting.
If the destination is a station with a different network
number, check if the network number is not in use.
C05F
H
This request cannot be executed to the target
programmable controller.
Correct the network number or PC number.
Correct the read/write request details.
C060
H
Incorrect request (For example, incorrect data was
specified for bit devices.)
Correct the request details and send it to the Ethernet
module again. (For example, correct the data.)
C061
H
The request data length does not match with the number of
data in the character (a part of text).
Check and correct the text or requested data length of the
Qn header. Then send the data to the Ethernet module
again.
C062
H
When writing was prohibited while the CPU was running,
data has been written to the remote I/O station using the
MC protocol (with a QnA-compatible 3E frame or 4E
frame).
To write data to the remote I/O station using the MC
protocol (with a QnA-compatible 3E frame or 4E frame),
select "Enable Write at RUN time" in the Ethernet
operation setting.
C070
H
The device memory cannot be extended for the target
station.
Read/write data without the device memory set for
extension.
Device memory can be extended only in an Ethernet
module-connected station and a Q/QnACPU via CC-Link
IE Controller Network, MELSECNET/H, or
MELSECNET/10.
C071
H
The number of device points for data read/write set for
modules other than a Q/QnACPU is too large.
Correct the number of device points for data read/write
and send the data to the Ethernet module again.
C072
H
Incorrect request (For example, a request for data
read/write in bit units has been issued to a word device.)
Check whether the data can be requested to the target
programmable controller CPU.
Correct the request details and send it to the Ethernet
module again. (For example, change the subcommand.)
C073
H
The Ethernet module cannot issue this request to the
target programmable controller CPU. (For example, the
number of double word access points cannot be specified
for modules other than a Q/QnACPU.)
Correct the request details.
C074
H
This request cannot be executed to the target
programmable controller CPU.
Correct the network number or PC number.
Correct the read/write request details.
C080
H
The destination IP address could not be obtained during
CC-Link IE Controller Network, CC-Link IE Field Network,
MELSECNET/H, MELSECNET/10 relay communications
or communications using data link instructions.
Set the Station No. <-> IP information in the Ethernet
module.
Change the conversion method for the CC-Link IE
Controller Network, CC-Link IE Field Network,
MELSECNET/H, and MELSECNET/10 relay
communication parameters.
C081
H
The termination process for the Ethernet module is in
process, and whether communications using data link
instructions have reached cannot be checked.
Finish all the communications to perform the termination
process of the Ethernet module.