CHAPTER 16 TROUBLESHOOTING
16
16.7 Error Code List
16.7.3 Error codes stored in the buffer memory
C0CF
H
System error (The OS detected an error.)
Follow the procedure below.
(1) Check if the Ethernet module, the power supply
module, and the CPU module are properly connected.
(2) Check if the operating environment of the Ethernet
module conforms to the general specifications of the
CPU module.
(3) Check if the power capacity is sufficient.
(4) Check if the hardware is normal according to the
manual for each module.
If the actions above do not solve the problem, please consult
your local Mitsubishi representative.
C0D0
H
Incorrect data length was specified. Correct the specified data length.
C0D1
H
The number of resends is incorrect. Correct the number of resends.
C0D2
H
The arrival monitoring time is incorrect. Correct the arrival monitoring time.
C0D3
H
The number of relay stations in CC-Link IE Controller
Network, CC-Link IE Field Network, MELSECNET/H, and
MELSECNET/10 exceeded the allowable range.
Check the specified value for the communication
destination.
Correct the settings in the Station No. <-> IP information
for the stations between the own station and the
communication destination.
C0D4
H
The number of relay stations in CC-Link IE Controller
Network, CC-Link IE Field Network, MELSECNET/H, and
MELSECNET/10 exceeded the allowable range.
Check the specified value for the communication
destination.
Correct the settings in the Station No. <-> IP information
for the stations between the own station and the
communication destination.
C0D5
H
The number of retries is incorrect. Correct the number of retries.
C0D6
H
The network number or station number is incorrect.
Correct the settings for the communication destination.
Correct the specified value for the communication
destination.
C0D7
H
Data were sent without the initial process completed.
Set the parameters with the programming tool and write
them to the CPU module. Then perform communications
with the connected device.
Wait for normal completion of the initial process before
performing communications with the connected device.
C0D8
H
The number of blocks exceeded the range. Correct the specified value for the number of blocks.
C0D9
H
The subcommand value is incorrect. Correct the specified value for the subcommand.
C0DA
H
A response to the PING test could not be received within
the time of the communication time check.
Correct the IP address and host name of the Ethernet
module where the PING test is executed.
Enable the Ethernet module where the PING test is
executed to perform communications. (Complete the initial
process.)
C0DB
H
The IP address and host name of the Ethernet module for
the PING test are incorrect.
Correct the IP address and host name of the Ethernet
module to perform the PING test.
C0DC
H
System error (The OS detected an error.)
Follow the procedure below.
(1) Check if the Ethernet module, the power supply
module, and the CPU module are properly connected.
(2) Check if the operating environment of the Ethernet
module conforms to the general specifications of the
CPU module.
(3) Check if the power capacity is sufficient.
(4) Check if the hardware is normal according to the
manual for each module.
If the actions above do not solve the problem, please consult
your local Mitsubishi representative.
Error code Error description Action