296
C17F
H
An error was returned from the DNS server.
Check if the IP address of the DNS server is correct.
Check if the mail server names (SMTP server names and
POP server names) are correct.
Check with the network administrator if the DNS function
of the server specified in the DNS setting is properly
operating.
C180
H
The device specified in "Condition Device" in "News
Setting" is outside the range set in the [Device] tab of the
PLC parameter window.
Correct the device settings in the PLC parameter window
and specify the condition devices within the range of the
device settings.
C1A0
H
An illegal request was made.
Try again.
If the same error occurs, the Ethernet module may have a
hardware error. Please consult your local Mitsubishi
representative.
C1A2
H
A response to the request could not be received. Check and correct the response waiting time.
C1A4
H
A request or subrequest is incorrect. Correct the request and subrequest.
C1A5
H
The specified target station or clear target is incorrect. Correct the specified target station or clear target.
C1A6
H
The specified connection number is incorrect.
Specify the connection number within the range of 1 to 16.
Do not select the connection number 8 or 16 when using
the pairing open method.
C1A7
H
The specified network number is incorrect. Correct the specified network number.
C1A8
H
The specified station number is incorrect. Correct the specified station number.
C1A9
H
The specified device number is incorrect. Correct the specified device number.
C1AA
H
The specified device name is incorrect. Correct the specified device name.
C1AC
H
The specified number of resends is incorrect. Correct the number of resends.
C1AD
H
The specified data length is incorrect. Correct the specified data length.
C1AE
H
The send/receive data length and header length are
incorrect.
Correct the specified send/receive data length and header
length to values within the allowable ranges.
The send/receive data length needs to be equal to or
longer than the header length.
C1AF
H
The specified port number is incorrect. Correct the specified port number.
C1B0
H
The open process of the specified connection has been
already completed.
Perform the close process before the open process.
C1B1
H
The open process of the specified connection has not been
completed.
Perform the open process.
C1B2
H
The OPEN or CLOSE instruction is being executed in the
specified connection.
Try again after the OPEN or CLOSE instruction is
completed.
C1B3
H
Another send or receive instruction is being executed in
the specified channel.
Change the channel number.
Try again after the send or receive instruction is
completed.
C1B4
H
The specified arrival monitoring time is incorrect.
Set the arrival monitoring time to a value within the
allowable range.
C1B5
H
Data could not be received within the specified arrival
monitoring time.
Correct the specified arrival monitoring time.
C1B6
H
The specified send mail address number is incorrect.
Correct the specified send mail address number.
Correct the send mail address setting in the parameter
setting.
C1B7
H
A reading operation was executed while no receiving e-
mail was stored in the mail buffer data area.
If there is an mail received in the mail information, execute
the MRECV instruction.
C1B8
H
The RECV instruction was executed for the channel that
had not received data.
Correct the execution condition of the RECV instruction.
Correct the channel number.
Error code Error description Action