298
C403
H
Simultaneous dedicated instructions execution error
Do not execute dedicated instructions which do not
support simultaneous execution.
Correct the specified connection number and execute the
dedicated instruction again.
C404
H
Protocol cancel request error
Check the canceled protocol in the control data of the
ECPRTCL instruction (execution count result) and
eliminate the cause of the cancellation.
C405
H
Protocol number setting error
Correct the specified protocol number and execute the
protocol again.
C406
H
Continuous protocol execution count setting error
Correct the number of protocols to be executed
continuously and execute the protocol again.
C407
H
Connection number setting error
Correct the specified connection number and execute the
protocol again.
Correct the connection setting of the specified connection
number and execute the protocol again.
C410
H
Receive wait timeout error
Check if the cable is disconnected.
Correct the connection setting of the specified connection
number and execute the protocol again.
Check that there is no error in the connected device.
Check that the sending from the connected device is not
interrupted.
Check that there is no data lost due to a receive error.
Check that there is no error in the data (packet) sent by
the connected device.
C411
H
Packet size error
Check the data sent by the connected device.
To send data that exceeds 2046 bytes from the connected
device, divide the data into several parts and send them
separately.
C417
H
Data length setting error, data quantity setting error
Check the maximum allowable data length and specify the
maximum length or less in the data length storage area.
Check the maximum allowable data quantity, and specify
the maximum quantity or less in the data quantity storage
area.
C420
H
Flash ROM write error
Write the data again.
If an error still occurs even after rewriting, replace the
module.
C421
H
Flash ROM write count over limit error
Replace the module because the number of writes
exceeded the limit.
C430
H
Protocol setting data writing during the ECPRTCL
instruction execution
If the ECPRTCL instruction is under execution, cancel the
instruction and write the protocol setting data.
C431
H
Connection close during the ECPRTCL instruction
execution
Check the operation of the connected device.
Check the connection open status with the connected
device.
Open the connection with the connected device again and
execute the instruction.
D000
H
to
DFFF
H
(Errors detected by CC-Link IE Field Network) Refer to the manual for each module.
E000
H
to
EFFF
H
(Errors detected by CC-Link IE Controller Network) Refer to the manual for each module.
F000
H
to
FFFF
H
(Errors detected by the MELSECNET/H and
MELSECNET/10 network system)
Refer to the MELSECNET/H or MELSECNET/10 network
system reference manual, and take corrective action.
Error code Error description Action