Appendix 1 Processing Time
[Calculation example 1]
The time between the E71 receiving request data from a personal computer and it completing reading when the
E71 communicates with the personal computer in TCP/IP and reads 100-point data of an ASCII code from the
data register (D) in the own station (unit: ms)
Assume that the scan time of the E71-connected station is 10ms, the command data length is 21 words, and the
response data length is 211 words.
14.37 + ACK processing time of the connected device (ms)
3.3 + (0.0046 (21 + 211)) + 10 1 + ACK processing time of the connected device
[Calculation example 2]
The time between the E71 receiving request data from a personal computer and it completing writing when the
E71 communicates with the personal computer in TCP/IP and writes 100-point data of an ASCII code to the data
register (D) in the own station (unit: ms)
Assume that the scan time of the E71-connected station is 10ms, the command data length is 221 words, the
response data length is 11 words, and writing during RUN is enabled.
14.99 (ms) + ACK processing time of the connected device
3.3 + (0.0073 (221 + 11)) + 10 1 + ACK processing time of the connected device