36
30
(1E
H
)
Initial process
parameter setting
area (For
reinitialization)
TCP Maximum Segment Transmission setting area
•0
H
: Enable TCP Maximum Segment Size Option transmission
•8000
H
: Disable TCP Maximum Segment Size Option transmission
Re-initialization makes the set value effective.
8000
H
31
(1F
H
)
Communication condition setting (Ethernet Operation Setting) area
Communication data code setting (b1)
0: Binary Code
1: ASCII Code
TCP existence confirmation setting (b4)
0: Use the Ping
1: Use the KeepAlive
Send frame setting (b5)
0: Ethernet
1: IEEE 802.3
Setting of write enable/disable at RUN time (b6)
0: Disable
•1: Enable
Initial timing setting (b8)
0: Do not wait for OPEN (Communications impossible at STOP time)
1: Always wait for OPEN (Communication possible at STOP time)
Reinitialization specification (b15)
0: Reinitialization process complete (reset by the system)
1: Reinitialization process request (set by the user)
Bits other than those described above are reserved for system use.
0
H
Address
Application Name Initial value
Programming
tool setting
applicability
Decimal
(Hexadecimal)