45
CHAPTER 3 SPECIFICATIONS
3
3.5 Buffer Memory
3.5.2 List of buffer memory addresses
20480
(5000
H
)
Connection status
storage area
Connection
status
information
area
Open completion signal
0: Open incomplete
1: Open completed
Connection No.1 (b0)
Connection No.2 (b1)
to
Connection No.16 (b15)
0
H
20481
(5001
H
)
System area 
20482
(5002
H
)
Open request signal
0: No open request
1: Open being requested
Connection No.1 (b0)
Connection No.2 (b1)
to
Connection No.16 (b15)
0
H
20483 and 20484
(5003
H
and 5004
H
)
System area 
20485
(5005
H
)
Fixed buffer
information
area
Fixed buffer reception status signal
0: Data not received
1: Data being received
Connection No.1 (b0)
Connection No.2 (b1)
to
Connection No.16 (b15)
0
H
20486
(5006
H
)
Remote
password
status
storage
area
Remote password status
0: Unlock status/no remote password setting
1: Lock status
Connection No.1 (b0)
Connection No.2 (b1)
to
Connection No.16 (b15)
0
H
20487
(5007
H
)
System port
information area
Remote
password
status
storage
area
Remote password status
0: Unlock status/no remote password setting
1: Lock status
Auto-open UDP port (b0)
MELSOFT application transmission port (UDP) (b1)
MELSOFT application transmission port (TCP) (b2)
FTP transmission port (b3)
0
H
20488
(5008
H
)
System port
use
prohibited
designation
area
System port use prohibited designation
0: Use allowed
1: Use prohibited
Auto-open UDP port (b0)
MELSOFT application transmission port (UDP) (b1)
MELSOFT application transmission port (TCP) (b2)
0
H
20489 to 20591
(5009
H
to 506F
H
)
System area 
Address
Application Name Initial value
Programming
tool setting
applicability
Decimal
(Hexadecimal)

Table of Contents