EasyManua.ls Logo

Mitsubishi Electric Q170MSCPU-S1 - Daily Inspection

Mitsubishi Electric Q170MSCPU-S1
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 - 4
6 INSPECTION AND MAINTENANCE
6.2 Daily Inspection
The items that must be inspected daily are shown below.
Table 6.1 Daily Inspection
Item Inspection item Inspection Criterion Action
1
Mounting of Motion
controller
Check that the fixing
screws are not loose and
the cover is not dislocated.
The screws and cover must be mounted securely.
Retighten the
screws.
2 Mounting of base unit
3
Installation of Motion
modules and I/O
modules
Check that the module is
not dislocated and the unit
fixing hook is engaged
securely.
The module fixing hook must be engaged and installed
correctly.
Securely
engaged the
module fixing
hook.
4 Connecting conditions
Check for loose terminal
screws.
Screws should not be loose.
Retighten the
terminal screws.
Check the distance
between solderless
terminals.
The proper clearance should be provided between solderless
terminals.
Correct.
Check the connector part of
the cable.
Connections should not be loose.
Retighten the
connector fixing
screws.
5
Module indication LED
Motion controller
[POWER]
LED
Check that the LED is ON.
The LED must be ON.
(Abnormal if the LED is OFF.).
Refer to Section
2.5.1
[MODE] LED Check that the LED is ON.
The LED must be ON.
(Abnormal if the LED is OFF or flickering.)
[RUN] LED
Check that the LED is ON
in RUN status.
The LED must be ON.
(Abnormal if the LED is OFF.)
[ERR.] LED Check that the LED is OFF.
The LED must be OFF.
(Abnormal if the LED is ON or flickering.)
[BAT.] LED Check that the LED is OFF.
The LED must be OFF.
(Abnormal if the LED is ON (yellow).)
Normal
Steady "RUN" display.
(Abnormal if "RUN" does not display or incorrect display.)
Steady "STP" display.
(Abnormal if "STP" does not display or incorrect display.)
Battery error
warning
(2.7V or less)
"BT1" does not display.
(Abnormal if steady "BT1" display.)
Refer to Section
6.5
Battery error
warning
(2.5V or less)
"BT2" does not display.
(Abnormal if steady "BT2" display.)
WDT error
" . . . " does not display.
(Abnormal if steady " . . ." display.)
Refer to Section
2.5.1
Others
" AL" does not flash.
(Abnormal if " . . ." flashes.)
I/O module
Input LED
Check that the LED is
ON/OFF.
The LED must be ON when the input power is turned ON.
The LED must be OFF when the input power is turned OFF.
(Abnormal if the LED does not turn ON or turn OFF as
indicated above.)
Refer to
"I/O Module
Type Building
Block User's
Manual".
Output LED
Check that the LED is
ON/OFF.
The LED must be ON when the output power is turned ON.
The LED must be OFF when the output power is turned OFF.
(Abnormal if the LED does not turn ON or turn OFF as
indicated above.)

Table of Contents

Other manuals for Mitsubishi Electric Q170MSCPU-S1