2 - 48
2 SYSTEM CONFIGURATION
(2) Names of Parts and Setting
This section describes the names of the parts of each power module.
• Q61P (100 to 240VAC input, 5VDC 6A output)
• Q62P (100 to 240VAC input, 5VDC 3A/24VDC 0.6A output)
• Q63P (24VDC input, 5VDC 6A output)
• Q64PN (100 to 240VAC input, 5VDC 8.5A output)
Q62P POWER
(FG)
(LG)
N
INPUT
L
ERR.
+-
L
100-240VAC
50/60Hz 105VA
INPUT
100-240VAC
OUTPUT 5VDC 3A/ 24VDC 0.6A
24VDC
0.5A
24G
+24V
Q62P
2)
3)
4)
5)
7)
8)
1)
10)
9)
6)
(Q62P only)
No. Name Application
1)
POWER
LED
AC input
power supply
ON (green) : Normal (5VDC output, momentary power failure within 20ms)
OFF : • AC power supply is ON, however, the power supply module is out of order.
(5VDC error, overload, internal circuit failure, blown fuse)
• AC power supply is not ON
• Power failure (including an momentary power failure of more than 20ms)
DC input
power supply
ON (green) : Normal (5VDC output, momentary power failure within 10ms)
OFF : • DC power supply is ON, however, the power supply module is out of order.
(5VDC error, overload, internal circuit failure, blown fuse)
• DC power supply is not ON
• Power failure (including an momentary power failure of more than 10ms)
2) ERR
terminals
Normally OFF when loaded in an extension base unit.
3) FG terminal Ground terminal connected to the shield pattern of the printed circuit board.
4) LG terminal
Grounding for the power supply filter. The potential of Q61P, Q62P, and Q64PN terminal
is 1/2 of the input voltage.
5) Power input terminals
• Power input terminals connected to a power supply of 100VAC to 200VAC.
(Q61P, Q62P, Q64PN)
• Power input terminals connected to a power supply of 24VDC. (Q63P)
6)
+24V, 24G terminals
(Q62P only)
Used to supply 24VDC power to inside the output module. (using external wiring)
7) Terminal screw M3.5 7 screw
8) Terminal cover Protective cover of the terminal block
9) Module fixing screw hole
Used to fix the module to the base unit.
M3
12 screw (user-prepared) (Tightening torque : 0.36 to 0.48
N•m)
10) Module mounting lever Used to load the module into the base unit.