158
APPX
Appendix 3 Buffer Memory Areas
CH1 Difference conversion status flag
The difference conversion status can be checked.
When the difference conversion starts after 'CH1 Difference conversion trigger' (Un\G470) is changed from No request (0) to
Trigger request (1), 'CH1 Difference conversion status flag' (Un\G408) corresponding to the channel turns to Converting
difference (1).
When 'CH1 Difference conversion trigger' (Un\G470) is changed from Trigger request (1) to No request (0), 'CH1 Difference
conversion status flag' (Un\G408) is changed from Converting difference (1) to Not converted (0).
'CH1 Difference conversion status flag' (Un\G408) is Converting difference (1) during the difference conversion; Not
converted (0) if not during the difference conversion.
Buffer memory address
The following shows the buffer memory address of this area.
•CH Difference conversion status flag
•CH Difference conversion status flag (in Q compatible mode)
CH1 Logging hold flag
The logging holding status can be checked.
For details on the logging function, refer to the following.
Page 61 Logging Function
When a state in which data is collected in 'CH1 Logging data' (Un\G10000 to Un\G10999) changes to the stop state, 'CH1
Logging hold flag' (Un\G409) is turned to ON (1).
When logging restarts by changing 'CH1 Logging hold request' (Un\G471) from ON (1) to OFF (0), 'CH1 Logging hold flag'
(Un\G409) is turned to OFF (0).
Buffer memory address
The following shows the buffer memory address of this area.
•CH Logging hold flag
•CH Logging hold flag (in Q compatible mode)
Monitor value Description
0 Not converted
1 Converting difference
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH11 CH12 CH13 CH14 CH15 CH16
408 608 808 1008 1208 1408 1608 1808 2008 2208 2408 2608 2808 3008 3208 3408
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH11 CH12 CH13 CH14 CH15 CH16
190 191 192 193 194 195 196 197
Monitor value Description
0 OFF
1 ON
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH11 CH12 CH13 CH14 CH15 CH16
409 609 809 1009 1209 1409 1609 1809 2009 2209 2409 2609 2809 3009 3209 3409
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH9 CH10 CH11 CH12 CH13 CH14 CH15 CH16
1016 1017 1018 1019 1020 1021 1022 1023