1 FUNCTIONS
1.8 Shift Function
When the I/O characteristics is adjusted in a channel where the input range of -10 to 10V is set by the shift function
*1 Because the value exceeds the range of -32768 to 32767, the value is fixed to 32767 (the upper limit value).
*2 These values are also applied to the case of digital output values (32 bits).
(1) 'CH1 Digital output value' (Un\G400)
+
'CH1 Conversion value shift amount' (Un\G472)
"+20000"
(2) 'CH1 Digital operation value' (Un\G402)
Voltage input Digital output value
*2
Digital operation value
-10 -32000 -12000
-5 -16000 4000
0 0 20000
5 16000 32767
*1
10 32000 32767
*1
(2)
(1)
32767
32000
(52000)
0
-32000
-12000
1050-5-10
Analog input voltage (V)